상세 보기
초록
The fall of potential method is typically used for measuring the ground resistance of large-sized grounding system. Because the distances between the test ground grid and auxiliary electrodes are limited in downtown areas, it is very difficult to measure acurately the ground resistance of large-sized ground system. Therefore the method of measuring the ground resistance using the vertically-placed auxiliary electrodes was investigated. Various simulations and trial tests were carried out in two-layer earth structure, and the validity of the method of measuring the ground resistance was examined.
- 제목
- 보조전극의 수직배치를 통한 접지저항 측정의 타당성 연구
- 제목 (타언어)
- Feasibility study on a Method for Measuring the Ground Resistance with the vertically-placed auxiliary electrodes
- 저자
- BOK HEE LEE
- 학회명
- 한국조명전기설비학회 추계학술대회
- 개최지
- 서울
- 학회 개최일
- 2011-11-23 ~ 2011-11-23