상세 보기
초록
Protection against indirect contact according to KS C IEC 60364-4-44 shall remain effective in the protected installation even in case of failures of surge protective devices. i.e., residual current operated circuit breakers(RCDs) shall not operate against surge voltages and currents. This paper presents a surge of un-tripping characteristics of RCDs against impulse voltages and currents according to KS C 4613 and KS C IEC 61009-1. As a consequence, it was found that most of domestic RCDs employed in this test are failed.
- 제목
- 누전차단기의 충격파부동작 특성의 분석
- 제목 (타언어)
- Analysis of Un-Tripping Characteristics of Residual Current Operated Circuit Breaker against Impulse Voltages and Currents
- 저자
- BOK HEE LEE
- 학회명
- 한국조명전기설비학회 춘계학술대회
- 개최지
- 무주
- 학회 개최일
- 2011-05-12 ~ 2011-05-13