배전용 전주의 접지 시스템에 대한 임펄스 특성

Impulse Characteristics of Grounding Systems for Distribution Concrete Pole
  • BOK HEE LEE

초록

This paper describes impulse grounding impedance and touch voltage when impulse current is injected to grounding systems for distribution concrete pole. Impulse grounding impedance is a significant factor in analyzing transient grounding impedance. The touch voltage is measured in four directions. The maximum touch voltage was 520V and the minimum touch voltage was 47.3V when the input current was 100A.

제목
배전용 전주의 접지 시스템에 대한 임펄스 특성
제목 (타언어)
Impulse Characteristics of Grounding Systems for Distribution Concrete Pole
저자
BOK HEE LEE
학회명
대한전기학회 하계학술대회