Non-uniform field breakdown characteristics of SF6/CF 4 mixtures at various pressures

  • HUH CHANG SU

초록

The breakdown and the corona inception voltages experiments of SF 6/CF4 mixtures in non-uniform field were performed. The experiments were carried out under AC, positive and negative standard lightning impulse (SLI) voltages. The point-plane electrode was used to make non-uniform field and gap distance was 3 mm. SF6/CF4 mixtures pressure ranged from 0.1 to 0.5 MPa and the percentage of SF6 and CF4 was 0, 20, 40, 60, 80 and 100%. Under positive SLI the breakdown voltage was increased slowly as pressure increasing but under negative SLI the breakdown voltage was increased slightly as pressure increasing. At low pressure the breakdown voltage of positive and negative SLI was similar. Under AC voltage the breakdown voltage was increased linearly but the corona inception voltage was saturated over 0.2 MPa. This paper suggests elementary data in Gas Insulated Systems. ?2007 IEEE.

제목
Non-uniform field breakdown characteristics of SF6/CF 4 mixtures at various pressures
저자
HUH CHANG SU
학회명
Proceedings of International Conference on Condition Monitoring and Diagnosis, CMD 2008
개최지
북경