상세 보기
초록
Electric shock is the accident caused by the current through a person or animal's body. That is characterized by the physiological effects. In this paper, we evaluate performance of protection against electric shocks for TT and TN grounding systems which are used by a low voltage consumer nowadays. The performance of protection against electric shocks for TT grounding system is very excellent in equipotential area of the third class grounding, but the performance is poor outside the equipotential area. The performance of protection against electric shocks for TN grounding system is excellent because the potential difference is less than 50V. Accordingly, the performance of protection for TN grounding system is good as compared with that for TT grounding system.
- 제목
- TT, TN접지계통의 감전보호 성능평가
- 제목 (타언어)
- Performance Evaluation of Protection against Electric Shocks for TT and TN Systems
- 저자
- BOK HEE LEE
- 학회명
- 2009년도 한국조명전기설비학회 추계학술대회
- 개최지
- COEX 신관 3층 Hall E (서울)
- 학회 개최일
- 2009-10-09 ~ 2009-10-09