대지저항률의 주파수 의존성

Frequency relativity of soil resistivity
  • BOK HEE LEE

초록

A new method measuring soil resistivity in frequency range of 5 ~ 500[㎑] using variable frequency inverter was presented, and soil resistivity was analysed by resistive and reactive components on the basis of magnitude and phase of measured ground impedance. The test lead arrangement was proposed to reduce the inductive coupling in test circuit for measuring the soil resistivity. The frequency dependence of soil resistivity was mainly caused by the inductive current flowing through grounding conductors over the frequency of 70[㎑]

제목
대지저항률의 주파수 의존성
제목 (타언어)
Frequency relativity of soil resistivity
저자
BOK HEE LEE
학회명
2003년도 한국조명전기설비학회 추계학술대회 논문집