This paper deals with frequency-dependent circuit parameters of metal conduits. The use of nonmagnetic conduit should be taken into account in order to reduce the inductance of battery charger distribution circuits. The frequency-dependent impedance of steel and aluminium conduits and switching surge voltages generated at the circuit consisted of steel and aluminium conduits were investigated. As a result, the switching surge voltages generated through Al conduit are significantly lower than those through steel conduit when DC fault current is interrupted.
- 제목
- 금속제 전선관 회로정수의 주파수의존성
- 제목 (타언어)
- Frequency-dependent circuit parameters of metal conduits
- 저자
- BOK HEE LEE
- 학회명
- 한국조명전기설비학회 추계학술대회
- 개최지
- 서울
- 학회 개최일
- 2012-10-19 ~ 2012-10-19