PVT-Air 연결식 ERV의 바이패스 모드 난방 에너지 절감 효과 분석
- 김창환;
- 최재솔;
- 오민석;
- 김기철;
- 김의종
초록
As PV power generation efficiency degrades according to an increase in cell temperatures, overall energy saving effects can be anticipated by using air type PVT and connecting the heated air from the PVT into an energy recovery ventilator (ERV). For such application, a ERV bypass mode can be applied to maximize energy saving effects during the heating period. The proposed system and corresponding control methods were compared to a reference case using TRNSYS simulation. A classroom equipped with typical electric heat pumps, ERVs, and ten PVT modules was simulated. Results showed that the proposed system reduced EHP energy consumption by more than 9% and improved PVT power production by more than 5%. Particularly, higher saving effects were found for the proposed bypass mode control than for the case of common ERV control.
키워드
- 제목
- PVT-Air 연결식 ERV의 바이패스 모드 난방 에너지 절감 효과 분석
- 제목 (타언어)
- Heating Energy Savings Analysis of Bypass Mode of a PVT-Air Coupled ERV
- 저자
- 김창환; 최재솔; 오민석; 김기철; 김의종
- 발행일
- 2023-02
- 유형
- Y
- 저널명
- 한국건축친환경설비학회 논문집
- 권
- 17
- 호
- 1
- 페이지
- 37 ~ 47