Network Responses to Coupled Current by Electrical Fast Transient Disturbances to UTP Cable

  • HUH CHANG SU

초록

Abstract?In order to study susceptibility of a computer network by using an Electrical Fast Transient/Burst (EFT/B) test method, we composed a simple computer network and tested it experimentally. The test setup consisted of two hubs, three Unshielded Twisted Pair (UTP) cables, and two desktop Personal Computers (PCs). By using a ping utility at the PC1, states of network signal transmission were monitored during the EFT/B generator’s execution time. A Capacitive Coupling Clamp (CCC) was introduced to wrap the UTP cable between hub1 and hub2, as described in the international standard IEC 61000-4-4. Pulsed current coupled by the CCC was picked up by using high-frequency current sensors and recorded by an oscilloscope. For the test, 1 kV, 2 kV, 4 kV, 6 kV, and 7 kV of the EFT/B generator’s open voltages were arbitrarily selected. At the 4 kV and 6 kV of the open voltages, coupled peak current on the UTP wire reached 2.8 A and 4 A, respectively, and network data losses were displayed but not for all the test shots. Moreover, there was no data loss at 7 kV even though lower voltages did induce data losses. The probable reason for these results is that the EFT/B was not effectively synchronized with the moments when the pings were sent and received in the Ethernet system.

제목
Network Responses to Coupled Current by Electrical Fast Transient Disturbances to UTP Cable
저자
HUH CHANG SU
학회명
AMEREM2018
개최지
UCSB in CA
학회 개최일
2018-08-27 ~ 2018-08-31