상세 보기
실측 데이터 기반 교육시설 건물의 Grey-box 모델 개발 및 MPC 시뮬레이션
- 최광원;
- 조재완
초록
This study aimed to develop a grey-box building model in a zone of a high-rise building on a university campus and to simulate model-based predictive control. Grey-box modeling was performed using various indoor and external environment data measured within a single-person office space on a high floor. The residence schedule was indirectly calculated using values such as indoor CO2 concentration and plug power. In addition, the catalog rating value was applied as the cooling energy value of the indoor 4-ways air conditioner as this could not be measured. Measurements were performed for approximately 4-weeks, and operating data of the heat pump and non-operating (i.e., free-floating) data were obtained according to the weekday and weekend schedules. The grey-box model was parameterized using the linear time-invariant and linear time-variant models. Both models showed good predictive performance with a root mean square error of less than 1°C in the 2-week estimation and 2-week validation results. Based on these results, an MPC simulation was performed. MPC simulation in a single zone were conducted for various electricity cost structures to derive quantitative electricity cost savings compared to those of feedback control.
키워드
- 제목
- 실측 데이터 기반 교육시설 건물의 Grey-box 모델 개발 및 MPC 시뮬레이션
- 제목 (타언어)
- Grey-box Model Develop and MPC Simulation of Campus Office Zone Based on Actual Measurement
- 저자
- 최광원; 조재완
- 발행일
- 2022-06
- 유형
- Y
- 저널명
- 한국태양에너지학회 논문집
- 권
- 42
- 호
- 3
- 페이지
- 103 ~ 115