Grounding impedance depends on the frequency of current flowing into a grounding system. Especially, the lightning gives a broad frequency spectrum from low frequency up to 1 MHz. So the grounding impedance related to high frequency current like lightning should be measured with high frequency source. In this paper, we described the grounding impedances of deeply-driven ground rods of 10 ~ 48 m long with respect to the frequency of injected currents and the feed point. For the experiments, we used the wideband power amplifier which can produce sinusoidal voltages with the frequency ranges of DC ~ 250 MHz. As a result, the longer the ground rod is, the lower the ground resistance is. However the grounding impedance of deeply-driven ground rod in the range of higher frequency is significantly increased. As a consequence, it is important to evaluate the high frequency performance of grounding systems for lightning protection.
- 제목
- 심매설 접지전극의 접지임피던스의 주파수의존성
- 제목 (타언어)
- Frequency Dependence of Grounding Impedances of the Deeply-driven Grond Rods
- 저자
- BOK HEE LEE
- 학회명
- 2008년도 한국조명전기설비학회 춘계학술대회
- 개최지
- 현대성우리조트 (강원도 횡성)
- 학회 개최일
- 2008-05-08 ~ 2008-05-09