ZnO 바리스터에 흐르는 누설전류의 주파수 의존성

Frequency dependences of leakage currents flowing through ZnO varistor
  • BOK HEE LEE

초록

This paper presents the frequency - dependent characteristics of leakage currents flowing through ZnO varistor. The leakage current - voltage () characteristic curves of the commercial ZnO varistor were measured. The resistive leakage current was increased with increasing the magnitude and frequency of the applied voltage in the low conduction region. The power losses of ZnO varistor increase as the frequency of applied voltage increases, because of the dielectric loss related to the frequency of the test voltage.

제목
ZnO 바리스터에 흐르는 누설전류의 주파수 의존성
제목 (타언어)
Frequency dependences of leakage currents flowing through ZnO varistor
저자
BOK HEE LEE
학회명
대한전기학회 하계학술대회