상세 보기
초록
This paper presents the characteristics of grounding impedance of counterpoises buried at various soil structures. Grounding impedance measurements were made by the Fall-of-Potential method. The experiments were carried out in 50 m counterpoise of 25 mm2 buried at a depth of 0.5 m. The test current was injected by the impulse generator having the front time of 1∼60 ㎲. As a result, the soil structures greatly influences on the grounding impedance characteristics of counterpoise. The transient grounding impedances strongly depend on the injection point and the front time of impulse current.
- 제목
- 대지구조에 따른 매설지선의 과도접지임피던스 특성
- 제목 (타언어)
- Transient impedance characteristics of counterpoise according to the soil structures
- 저자
- BOK HEE LEE
- 학회명
- 2009년도 한국조명전기설비학회 추계학술대회
- 개최지
- COEX 신관 3층 Hall E (서울)
- 학회 개최일
- 2009-10-09 ~ 2009-10-09