EMTP를 이용한 매설지선의 규약접지임피던스 해석

Analysis for the conventional impedance of counterpoise using EMTP
  • BOK HEE LEE

초록

When the lightning currents flow through the ground electrode, the grounding system should be evaluated by the grounding impedance rather than the ground resistance because a grounding system shows the transient impedance characteristic by the inductance of the ground electrode and the capacitance of the soil. The ratio of the peak values of electric potential and currents is the conventional impedance that shows the transient characteristic about impulse currents of the grounding system in a roundabout way. The grounding system having low conventional impedance is a fine grounding system with low electric potential when the lightning currents flow. In this paper the conventional impedance of the counterpoise is calculated by using the distributed parameter circuit model and embodied the distributed parameter circuit model by using the EMTP program. The adequacy of the distributed parameter model is examined by comparing the simulated and the measured results. The conventional impedance of the counterpoise is analyzed for first short stroke and subsequent short stroke currents.

제목
EMTP를 이용한 매설지선의 규약접지임피던스 해석
제목 (타언어)
Analysis for the conventional impedance of counterpoise using EMTP
저자
BOK HEE LEE
학회명
2009년도 한국조명전기설비학회 추계학술대회
개최지
COEX 신관 3층 Hall E (서울)
학회 개최일
2009-10-09 ~ 2009-10-09