배전계통의 고장이 배전용 피뢰기에 미치는 영향

The influence of distribution arrester caused by fault conditions of distribution system
  • BOK HEE LEE

초록

Abstract Kinds of most frequent faults happened on overhead distribution system are the single line-to-ground fault, the line-to-line fault and the two line-to-ground fault. In this study, the single line-to-ground fault, the line-to-line fault, two line-to-ground fault on three-phase four-wire overhead distribution system were experimentally simulated and characteristics of total leakage current of distribution arrester caused by these faults were investigated. Also, the changing aspect of total leakage current of distribution arrester caused by voltage variation was investigated. In a consequence, abnormal voltages caused by voltage variation, the line-to-line fault, the two line-to-ground fault have a little effect on total leakage current of ZnO arrester. But abnormal voltages caused by the single line-to-ground fault have an important effect on total leakage current of ZnO arrester.

제목
배전계통의 고장이 배전용 피뢰기에 미치는 영향
제목 (타언어)
The influence of distribution arrester caused by fault conditions of distribution system
저자
BOK HEE LEE
학회명
한국조명,전기설비학회 2004춘계학술대회