상세 보기
초록
In this study, thermodynamic performance of R432A and HCFC22 is measured in a heat pump bench tester under both air-conditioning and heat pumping conditions. R432A has no ozone depletion potential and very low greenhouse warming potential of less than 5. R432A also offers a similar vapor pressure to HCFC22 for 'drop-in' replacement. Test results showed that the coefficient of performance and capacity of R432A are 8.5-8.7% and 1.9-6.4% higher than those of HCFC22 for both conditions. The compressor discharge temperature of R432A is 14.1-17.3 °C lower than that of HCFC22 while the amount of charge for R432A is 50% lower than that of HCFC22 due to its low density. Overall, R432A is a good long term 'drop-in' environmentally friendly alternative to replace HCFC22 in residential air-conditioners and heat pumps due to its excellent thermodynamic and environmental properties. ? 2008 Elsevier Ltd. All rights reserved.
- 제목
- Performance of R432A to Replace HCFC22 in Residential Air-conditioners and Heat Pumps
- 저자
- DONGSOO JUNG
- 학회명
- Applied Thermal Engineering
- 개최지
- Purdue University
- 학회 개최일
- 2008-07-14 ~ 2008-07-17