상세 보기
FLS 단순 중첩 방식의 지열 응답 함수를 활용한 트랜시스 지열 교환기 모델
초록
FLS(finite line source)-based g-function has been used as an alternative of Eskilson’s original g-function. A proper generation of the g-function using FLS can be achieved by setting uniform borehole temperatures for all the boreholes lest the calculated g-function would be overestimated. In this paper, this condition has been neglected in order to rapidly generate the FLS-based g-function and to ease the programming process. A Trnsys generator of such a g-function has been developed. As expected, the g-function generated from the developed Trnsys generator overestimates the values in long-time regions, but simulation results are very similar to the well-known Trnsys DST(Duct Storage) model. The difference of g-function values in that regions has little affected the simulation results (±1°C) in a test case.
- 제목
- FLS 단순 중첩 방식의 지열 응답 함수를 활용한 트랜시스 지열 교환기 모델
- 제목 (타언어)
- A TRNSYS Ground Heat Exchangers Model Using a Simple Generator of the FLS–based g-function
- 저자
- KIM EUIJONG
- 학회명
- 대한 설비 공학회 하계 학술 대회
- 개최지
- 용평
- 학회 개최일
- 2015-06-24 ~ 2015-06-26