가변주파수 인버터를 이용한 접지임피던스 측정

  • BOK HEE LEE

초록

This paper presents a novel method for measuring the ground impedance in grounding systems. A square wave current was injected to the main grounding grid through auxiliary electrode, and the test current and ground potential rise(GPR) were measured using the band-pass filter. Ground impedance was calculated from the sinusoidal waveforms of the test current and GPR in frequency range of 20∼2100Hz. Also the resistance and reactance component of ground impedance were analyzed.

제목
가변주파수 인버터를 이용한 접지임피던스 측정
저자
BOK HEE LEE
학회명