상세 보기
초록
This paper presents the behaviors of transient and conventional grounding impedances of a deep-driven ground rods associated with the injection point of lightning impulse currents. The transient impedance of deep-driven ground rods under lightning impulse currents were higher than the static ground resistance. The transient grounding impedances strongly depend on the injection point and size of grounding electrodes and the rising time of impulse current. Reduction of ground system inductance is an important factor to lightning surge protection.
- 제목
- 심매설 접지전극의 전류인가위치에 따른 과도접지임피던스 특성
- 제목 (타언어)
- Transient impedance characteristics according to the injection position of deep-driven ground rods
- 저자
- BOK HEE LEE
- 학회명
- 2008년도 한국조명전기설비학회 춘계학술대회
- 개최지
- 현대성우리조트 (강원도 횡성)
- 학회 개최일
- 2008-05-08 ~ 2008-05-09