상세 보기
초록
SF6 is the most commonly used insulating gas in electrical systems. But In these days SF6 mixtures and alternative gas has been studied because of global warming. so although many studies have been carried out about binary gas mixtures with SF6, few studies were presented about breakdown characteristics of SF6/N2 mixtures. At present study the breakdown characteristics of SF6/N2 mixtures in Non-uniform field was performed. In this paper, breakdown experiment values and breakdown simulation values are compared. Streamer theory was used for predicting breakdown voltage. For accurate simulation field factor, this simulation apply E field utilization using cst program AC breakdown experiments in non-uniform field was performed to compare with the breakdown simulation values. The pressure range of gas mixtures was 0.4 ㎫ to 0.7 ㎫. The rod-plane was used and mixture ratio is SF6 20% : N2 80%. The gap lengths is 10㎜ to 70㎜. As pressure increase, this simulation value do not correspond to the experiment value. So this simulation apply to utilization factor using CST program In the result, it was observed that breakdown voltage increase as pressure and gap lengths increase. But with gap lengths increasing, the breakdown voltage is saturated. So simulation need surface roughness factor.
- 제목
- 초고압, 장갭의 불평등전계에서 SF6/N2혼합가스의 절연내력 시뮬레이션 및 실험값와의 비교
- 제목 (타언어)
- AC Breakdown Voltage Characteristics Simulation of SF?/N₂ in Non-uniform field of Extra High Voltage, Long gap
- 저자
- HUH CHANG SU
- 학회명
- 대한전기학회 2010년 하계학술대회
- 개최지
- BEXCO(부산)
- 학회 개최일
- 2010-07-14 ~ 2010-07-16