2층 대지구조에서 접지전극에 의한 전위간섭 분석

An analysis of potential interference due to grounding electrodes in two-layered soil structure
  • BOK HEE LEE

초록

When the fault current flows into an independent grounding electrode, potential interference occurs in adjacent grounding electrodes. Potential interference is generally studied in uniform soil but is not enough analyzed in two-layered soil structure. This paper presents a method to reduce potential interference of communication grounding system from due to grounding electrodes of lightning protection system in two-layered soil structure . As a result, it was found that the grounding electrodes to be interfered should be buried in soil with lower resistivity in two-layered soil structure.

제목
2층 대지구조에서 접지전극에 의한 전위간섭 분석
제목 (타언어)
An analysis of potential interference due to grounding electrodes in two-layered soil structure
저자
BOK HEE LEE
학회명
한국조명전기설비학회 2010 추계학술대회
개최지
서울 코엑스
학회 개최일
2010-09-29 ~ 2010-09-29