Component model calibration using typical AHU data for improved prediction of daily heat source energy consumption

Citations

WEB OF SCIENCE

6
Citations

SCOPUS

6

초록

Model predictive control (MPC) has the potential to reduce energy consumption during building operations by determining an optimal operating strategy in advance. However, the data acquired from operational buildings are insufficient to fit the models, leading to difficulties in calibrating the entire target system. Therefore, this study evaluates the impact of local calibration on the performance of heat source energy consumption prediction models using only AHU data typically collected in an operational building. This load-side calibrated model showed an accuracy of within 30% of the CVRMSE. Daily heat source consumption was predicted using the proposed model, which demonstrated superior explanatory power (R2 & AP; 0.95) compared to the initial uncalibrated model. Therefore, such a locally calibrated model developed with insufficient data has the potential to be used for MPC without installing additional sensors.

키워드

Gray -box modelingBuilding energy simulationModel calibrationLimited data environmentBUILDINGS
제목
Component model calibration using typical AHU data for improved prediction of daily heat source energy consumption
저자
Oh, Ju-HongPark, Seung-HoonKim, Eui-Jong
DOI
10.1016/j.jobe.2023.107376
발행일
2023-10-01
유형
Article
저널명
Journal of Building Engineering
76